Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Number of poles4
Rated voltage690 - 690V
DIN rail (top hat rail) mounting optionalNo
With under voltage releaseNo
Adjustment range undelayed short-circuit release375.0 - 3750A
Position of connection for main current circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementPush button
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive integratedNo
Overload release current setting100.0 - 250A
Degree of protection (IP)IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Integrated earth fault protectionYes
Type of electrical connection of main circuitConnection at separate chassis part
Rated permanent current Iu250A
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release150.0 - 2500A
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073666R1 | E2.2S 250 EKIP HI-TOUCH LSIG 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Number of poles

4

Rated voltage

690 .. 690V

DIN rail (top hat rail) mounting optional

With under voltage release

Adjustment range undelayed short-circuit release

375.0 .. 3750A

Position of connection for main current circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

Type of control element

Push button

Motor drive optional

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive integrated

Overload release current setting

100.0 .. 250A

Degree of protection (IP)

IP30

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

Rated permanent current Iu

250A

With switched-off indicator

Adjustment range short-term delayed short-circuit release

150.0 .. 2500A

Complete device with protection unit