Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA069474R1 | E2N/VF 1600 PR122VF In1600A 3p WMP 1000V

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Rated voltage
1000 .. 1000V
Rated permanent current Iu
1600A
Power loss
215W
Overload release current setting
640.0 .. 1600A
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Type of electrical connection of main circuit
Connection at separate chassis part
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
- .. -A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
With switched-off indicator
Integrated earth fault protection
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Complete device with protection unit
DIN rail (top hat rail) mounting optional