

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
- - -A
Motor drive optional
No
Adjustment range undelayed short-circuit release
- - -A
Adjustment range short-term delayed short-circuit release
- - -A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
With integrated under voltage release
No
Rated permanent current Iu
3200A
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Rated voltage
690 - 690V
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Front side
Motor drive integrated
No
Degree of protection (IP)
IP20
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
From same serie
1SDA065800R1 | T8V 3200 PR332/P LSIG In=3200A 4p F VR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
- .. -A
Motor drive optional
Adjustment range undelayed short-circuit release
- .. -A
Adjustment range short-term delayed short-circuit release
- .. -A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
-kA
With integrated under voltage release
Rated permanent current Iu
3200A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Front side
Motor drive integrated
Degree of protection (IP)
IP20
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
From same serie
We use cookies to enhance your experience.