Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • EATON

Technical specifications

Built-in depth70.5mm
Rated current50A
Rated voltage400V
Voltage typeAC
Frequency50 - 60Hz
Number of protected poles4
Connectable conductor cross section solid-core1 - 25mm²
Release characteristicZ
Power loss14.3W
Number of poles (total)4
Connectable conductor cross section multi-wired1 - 25mm²
Current limiting class3
Ambient temperature during operating-25 - 75°C
Over voltage category3
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V0kA
Width in number of modular spacings4
Flush-mounted installationNo
Degree of protection (IP)IP20
Pollution degree2
Concurrently switching neutral conductorYes
Rated insulation voltage Ui440V
Additional equipment possibleYes
Explosion-proofNo
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V0kA
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10kA

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

FAZ-Z50/4

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • EATON

Technical specifications

Built-in depth

70.5mm

Rated current

50A

Rated voltage

400V

Voltage type

AC

Frequency

50 .. 60Hz

Number of protected poles

4

Connectable conductor cross section solid-core

1 .. 25mm²

Release characteristic

Z

Power loss

14.3W

Number of poles (total)

4

Connectable conductor cross section multi-wired

1 .. 25mm²

Current limiting class

3

Ambient temperature during operating

-25 .. 75°C

Over voltage category

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

0kA

Width in number of modular spacings

4

Flush-mounted installation

Degree of protection (IP)

IP20

Pollution degree

2

Concurrently switching neutral conductor

Rated insulation voltage Ui

440V

Additional equipment possible

Explosion-proof

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

0kA

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10kA

Related products