Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • EATON

Technical specifications

Rated insulation voltage Ui500V
Voltage typeAC
Built-in depth75.5mm
Over voltage category3
Surge current capacity0.25kA
Current limiting class3
Release characteristicB
Frequency50 Hz
Pollution degree2
Degree of protection (IP)IP20
Width in number of modular spacings2
Number of protected poles1
Rated voltage240V
Concurrently switching neutral conductorYes
Rated short-circuit breaking capacity according to IEC 60947-20kA
With interlocking deviceNo
Flush-mounted installationNo
Rated impulse withstand voltage Uimp4kV
Anti-nuisance tripping versionNo
Ambient temperature during operating-25 - 40°C
Rated short-circuit breaking capacity Icn according to EN 61009-16kA
Disconnection characteristicUndelayed
Rated short-circuit breaking capacity according to EN 610096kA
Connectable conductor cross section solid-core1 - 25mm²
Connectable conductor cross section multi-wired1 - 25mm²
Rated current13A
Rated fault current0.03A
Leakage current typeA
Number of poles (total)2
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user