Technical specifications

Rated insulation voltage Ui500V
Rated voltage240V
Release characteristicB
Voltage typeAC
Built-in depth75.5mm
Current limiting class3
Over voltage category3
Surge current capacity0.25kA
Pollution degree2
Frequency50 Hz
Number of protected poles1
Connectable conductor cross section solid-core1 - 25mm²
Rated short-circuit breaking capacity according to IEC 60947-210kA
Concurrently switching neutral conductorYes
Rated short-circuit breaking capacity Icn according to EN 61009-110kA
Disconnection characteristicUndelayed
Flush-mounted installationNo
Degree of protection (IP)IP20
Anti-nuisance tripping versionNo
Connectable conductor cross section multi-wired1 - 25mm²
Rated impulse withstand voltage Uimp4kV
Width in number of modular spacings2
With interlocking deviceNo
Ambient temperature during operating-25 - 40°C
Rated short-circuit breaking capacity according to EN 6100910kA
Rated current40A
Rated fault current0.3A
Leakage current typeAC
Number of poles (total)2

Related products