Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Overload release current setting250 - 320A
Number of auxiliary contacts as change-over contact0
With integrated under voltage releaseNo
Type of electrical connection of main circuitScrew connection
Type of control elementRocker lever
Motor drive integratedNo
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Adjustment range undelayed short-circuit release1920 - 19200A
Adjustment range short-term delayed short-circuit release0 - 0A
Device constructionBuilt-in device plug-in technique
With switched-off indicatorNo
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionNo
Rated permanent current Iu320A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user