Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
NZMH3-4-VE630-SVE

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
0
Overload release current setting
315 .. 630A
Adjustment range short-term delayed short-circuit release
210 .. 2205A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Complete device with protection unit
Type of control element
Rocker lever
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Front side
Device construction
Built-in device plug-in technique
Type of electrical connection of main circuit
Screw connection
Motor drive integrated
With under voltage release
With switched-off indicator
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Adjustment range undelayed short-circuit release
1260 .. 5040A
Degree of protection (IP)
IP20