Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Position of connection for main current circuitFront side
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Overload release current setting315 - 630A
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP20
Type of electrical connection of main circuitScrew connection
Motor drive integratedNo
Adjustment range undelayed short-circuit release1260 - 5040A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionYes
With switched-off indicatorNo
Type of control elementRocker lever
With under voltage releaseNo
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release472 - 4410A
Complete device with protection unitYes
Rated permanent current Iu630A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA