Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Overload release current setting125 - 250A
Number of auxiliary contacts as normally closed contact0
Type of control elementRocker lever
Adjustment range short-term delayed short-circuit release250 - 2500A
Motor drive optionalYes
Adjustment range undelayed short-circuit release500 - 2750A
Integrated earth fault protectionNo
Degree of protection (IP)IP20
Type of electrical connection of main circuitScrew connection
DIN rail (top hat rail) mounting optionalNo
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Device constructionBuilt-in device plug-in technique
Position of connection for main current circuitFront side
With under voltage releaseNo
With switched-off indicatorNo
Rated permanent current Iu250A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user