Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitScrew connection
Adjustment range short-term delayed short-circuit release1250 - 12500A
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally open contact0
Type of control elementRocker lever
Adjustment range undelayed short-circuit release2500 - 15000A
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorNo
Degree of protection (IP)IP20
Motor drive integratedNo
With under voltage releaseNo
Integrated earth fault protectionNo
Overload release current setting630 - 1250A
Position of connection for main current circuitFront side
Complete device with protection unitYes
Rated permanent current Iu1250A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA