ModelIntegrated connector
Suitable for circuit integrityNo
Mounting perforation in bottomYes
Useful cross section65500mm²
Load test type according to IEC 61537Type II
Safe working load according to IEC 61537 with support spacing 2.0 m2340N/m
Safe working load according to IEC 61537 with support spacing 1.5 m3000N/m
Possible support spacing1.5 - 4m
Safe working load according to IEC 61537 with support spacing 2.5 m1740N/m
Safe working load according to IEC 61537 with support spacing 4.0 m300N/m
Safe working load according to IEC 61537 with support spacing 3.0 m1200N/m
Surface protectionContinuously galvanized