Aleta.hr
Announcement

Registration is currently available to business customers only (B2B).

Details

  • •ODVODNIK PRENAPONA,TIP T2, 440V, UTICNI
  • •Earthing, lightning and surge protection
  • •Surge protection device for power supply systems
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

With remote signalling contactNo
Mounting methodDIN rail (top hat rail) 35 mm
Nominal voltage DC-V
Number of conductors (without earthing)4
Category type 2Yes
Construction size4 modular spacing
Voltage protection level2.1kV
Voltage protection level L-N1.8kV
Max. PV-voltage-V
Integrated backup fuseNo
Max. continuous voltage DC-V
Voltage protection level N-PE1.4kV
Max. continuous voltage AC440V
Signalling at the deviceOptic
System configuration TTYes
System configuration TN-SYes
System configuration TN-C-SYes
System configuration otherNo
Max. conductor cross section solid (solid, stranded)25mm²
System configuration DCNo
System configuration TN-CNo
Max. conductor cross section flexible (fine-strand)16mm²
System configuration ITNo
System configuration TNYes
Short-circuit breaking capacity (Isccr)100kA
Integrated short-circuit protection selective to fuse gG-A
Max. overcurrent protection device, parallel connection (fuse)125A
Max. discharge surge current (8/20)160kA
Max. overcurrent protection device, series connection (fuse)125A
Leakage-current freeYes
Integrated short-circuit protectionNo
Nominal discharge surge current (8/20)20kA
Nominal voltage AC230V
Degree of protection (IP)IP20
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as