Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Mounting methodDIN rail (top hat rail) 35 mm
With remote signalling contactYes
Construction size4 modular spacing
Number of conductors (without earthing)4
Voltage protection level2.1kV
Nominal voltage AC230V
Voltage protection level L-N1.8kV
Category type 2Yes
Nominal voltage DC-V
Nominal discharge surge current (8/20)20kA
Signalling at the deviceOptic
Max. continuous voltage AC440V
Max. conductor cross section flexible (fine-strand)16mm²
Voltage protection level N-PE1.4kV
Leakage-current freeYes
Integrated backup fuseNo
System configuration TNYes
System configuration DCNo
Short-circuit breaking capacity (Isccr)100kA
Max. discharge surge current (8/20)160kA
Integrated short-circuit protectionNo
Degree of protection (IP)IP20
System configuration TN-C-SYes
Max. conductor cross section solid (solid, stranded)25mm²
System configuration otherNo
Max. PV-voltage-V
System configuration TN-SYes
Max. continuous voltage DC-V
Max. overcurrent protection device, parallel connection (fuse)125A
System configuration TTYes
Integrated short-circuit protection selective to fuse gG-A
Max. overcurrent protection device, series connection (fuse)125A
System configuration TN-CNo
System configuration ITNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB803973R1500 | OVR T2 3N 40-440 P TS QS

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Mounting method

DIN rail (top hat rail) 35 mm

With remote signalling contact

Construction size

4 modular spacing

Number of conductors (without earthing)

4

Voltage protection level

2.1kV

Nominal voltage AC

230V

Voltage protection level L-N

1.8kV

Category type 2

Nominal voltage DC

-V

Nominal discharge surge current (8/20)

20kA

Signalling at the device

Optic

Max. continuous voltage AC

440V

Max. conductor cross section flexible (fine-strand)

16mm²

Voltage protection level N-PE

1.4kV

Leakage-current free

Integrated backup fuse

System configuration TN

System configuration DC

Short-circuit breaking capacity (Isccr)

100kA

Max. discharge surge current (8/20)

160kA

Integrated short-circuit protection

Degree of protection (IP)

IP20

System configuration TN-C-S

Max. conductor cross section solid (solid, stranded)

25mm²

System configuration other

Max. PV-voltage

-V

System configuration TN-S

Max. continuous voltage DC

-V

Max. overcurrent protection device, parallel connection (fuse)

125A

System configuration TT

Integrated short-circuit protection selective to fuse gG

-A

Max. overcurrent protection device, series connection (fuse)

125A

System configuration TN-C

System configuration IT

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.