Technical specifications
Nominal voltage AC
230V
With remote signalling contact
Nominal voltage DC
-V
Max. PV-voltage
-V
Signalling at the device
Optic
Max. continuous voltage AC
275V
Voltage protection level
1.4kV
Voltage protection level N-PE
1.4kV
Number of conductors (without earthing)
1
Category type 2
Construction size
1 modular spacing
Max. continuous voltage DC
-V
Mounting method
DIN rail (top hat rail) 35 mm
Voltage protection level L-N
1.4kV
Nominal discharge surge current (8/20)
20kA
Degree of protection (IP)
IP20
Integrated backup fuse
System configuration IT
System configuration DC
Max. discharge surge current (8/20)
40kA
Max. conductor cross section flexible (fine-strand)
25mm²
System configuration TN-S
System configuration other
System configuration TT
System configuration TN-C
Max. conductor cross section solid (solid, stranded)
35mm²
System configuration TN
Short-circuit breaking capacity (Isccr)
100kA
System configuration TN-C-S