Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)IP20
Mounting methodDIN rail (top hat rail) 35 mm
Construction size4 modular spacing
Number of conductors (without earthing)4
Max. continuous voltage AC275V
Signalling at the deviceOptic
Max. continuous voltage DC-V
Voltage protection level2kV
Nominal voltage AC400V
Voltage protection level L-N1.8kV
Max. conductor cross section flexible (fine-strand)25mm²
Max. conductor cross section solid (solid, stranded)35mm²
Integrated backup fuseYes
With remote signalling contactYes
Nominal voltage DC-V
Nominal discharge surge current (8/20)20kA
Voltage protection level N-PE2kV
System configuration DCNo
System configuration TNYes
System configuration TN-CNo
System configuration TTYes
System configuration ITNo
System configuration TN-SYes
System configuration otherNo
System configuration TN-C-SYes
Max. PV-voltage-V
Category type 2Yes
Max. discharge surge current (8/20)80kA
Short-circuit breaking capacity (Isccr)100kA
Max. overcurrent protection device, parallel connection (fuse)160A
Max. overcurrent protection device, series connection (fuse)125A
Integrated short-circuit protectionNo
Integrated short-circuit protection selective to fuse gG-A
Leakage-current freeYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB815704R3700 | OVR T2 3N 40-440s P TS QS

Main Product Image

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)

IP20

Mounting method

DIN rail (top hat rail) 35 mm

Construction size

4 modular spacing

Number of conductors (without earthing)

4

Max. continuous voltage AC

275V

Signalling at the device

Optic

Max. continuous voltage DC

-V

Voltage protection level

2kV

Nominal voltage AC

400V

Voltage protection level L-N

1.8kV

Max. conductor cross section flexible (fine-strand)

25mm²

Max. conductor cross section solid (solid, stranded)

35mm²

Integrated backup fuse

With remote signalling contact

Nominal voltage DC

-V

Nominal discharge surge current (8/20)

20kA

Voltage protection level N-PE

2kV

System configuration DC

System configuration TN

System configuration TN-C

System configuration TT

System configuration IT

System configuration TN-S

System configuration other

System configuration TN-C-S

Max. PV-voltage

-V

Category type 2

Max. discharge surge current (8/20)

80kA

Short-circuit breaking capacity (Isccr)

100kA

Max. overcurrent protection device, parallel connection (fuse)

160A

Max. overcurrent protection device, series connection (fuse)

125A

Integrated short-circuit protection

Integrated short-circuit protection selective to fuse gG

-A

Leakage-current free