Aleta.hr

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Max. continuous voltage AC440V
Mounting methodDIN rail (top hat rail) 35 mm
Voltage protection level1.4kV
Nominal voltage DC-V
With remote signalling contactYes
Nominal discharge surge current (8/20)20kA
Category type 2Yes
Number of conductors (without earthing)4
Nominal voltage AC400V
Construction size4 modular spacing
Voltage protection level L-N1.4kV
Degree of protection (IP)IP20
Max. continuous voltage DC-V
Signalling at the deviceOptic
Max. PV-voltage-V
Max. conductor cross section flexible (fine-strand)25mm²
Max. conductor cross section solid (solid, stranded)35mm²
Voltage protection level N-PE1.4kV
System configuration TNYes
Integrated backup fuseYes
Short-circuit breaking capacity (Isccr)100kA
System configuration otherNo
Integrated short-circuit protection selective to fuse gG-A
System configuration ITNo
System configuration TN-SYes
Integrated short-circuit protectionNo
System configuration TTYes
System configuration TN-CNo
System configuration DCNo
Leakage-current freeYes
System configuration TN-C-SYes
Max. overcurrent protection device, parallel connection (fuse)160A
Max. discharge surge current (8/20)80kA
Max. overcurrent protection device, series connection (fuse)125A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB815708R3700 | OVR T2 3N 80-440s P TS QS

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Max. continuous voltage AC

440V

Mounting method

DIN rail (top hat rail) 35 mm

Voltage protection level

1.4kV

Nominal voltage DC

-V

With remote signalling contact

Nominal discharge surge current (8/20)

20kA

Category type 2

Number of conductors (without earthing)

4

Nominal voltage AC

400V

Construction size

4 modular spacing

Voltage protection level L-N

1.4kV

Degree of protection (IP)

IP20

Max. continuous voltage DC

-V

Signalling at the device

Optic

Max. PV-voltage

-V

Max. conductor cross section flexible (fine-strand)

25mm²

Max. conductor cross section solid (solid, stranded)

35mm²

Voltage protection level N-PE

1.4kV

System configuration TN

Integrated backup fuse

Short-circuit breaking capacity (Isccr)

100kA

System configuration other

Integrated short-circuit protection selective to fuse gG

-A

System configuration IT

System configuration TN-S

Integrated short-circuit protection

System configuration TT

System configuration TN-C

System configuration DC

Leakage-current free

System configuration TN-C-S

Max. overcurrent protection device, parallel connection (fuse)

160A

Max. discharge surge current (8/20)

80kA

Max. overcurrent protection device, series connection (fuse)

125A

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.