18852
Code: 1690403

18852

Current limiting class
-
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
-kA
Number of poles (total)
3
Rated current
32A
Built-in depth
47mm
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
50kA
Release characteristic
D
Rated voltage
415V
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
100kA
Frequency
50 .. 60Hz
Rated insulation voltage Ui
690V
Rated impulse withstand voltage Uimp
8kV
Number of protected poles
3
Voltage type
AC/DC
Over voltage category
4
Concurrently switching neutral conductor
Additional equipment possible
Width in number of modular spacings
4.5
Pollution degree
3
Connectable conductor cross section solid-core
1.5 .. 50mm²
Degree of protection (IP)
IP20
Flush-mounted installation
Connectable conductor cross section multi-wired
1 .. 35mm²
Explosion-proof
Ambient temperature during operating
-30 .. 70°C