Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • SCHNEIDER

Technical specifications

Adjustment range short-term delayed short-circuit release- - -A
Type of electrical connection of main circuitScrew connection
Adjustment range undelayed short-circuit release945 - 6300A
Rated voltage690 - 690V
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu630A
Suitable for DIN rail (top hat rail) mountingNo
With integrated under voltage releaseNo
Position of connection for main current circuitFront side
Device constructionBuilt-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Overload release current setting252 - 630A
Number of poles3
Power loss30W
Number of auxiliary contacts as normally open contact0
Integrated earth fault protectionNo
Number of auxiliary contacts as normally closed contact0
Motor drive integratedNo
Degree of protection (IP)IP40
Complete device with protection unitYes
Number of auxiliary contacts as change-over contact0
Motor drive optionalYes
With switched-off indicatorYes
Type of control elementToggle
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

33460

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • SCHNEIDER

Technical specifications

Adjustment range short-term delayed short-circuit release

- .. -A

Type of electrical connection of main circuit

Screw connection

Adjustment range undelayed short-circuit release

945 .. 6300A

Rated voltage

690 .. 690V

DIN rail (top hat rail) mounting optional

Rated permanent current Iu

630A

Suitable for DIN rail (top hat rail) mounting

With integrated under voltage release

Position of connection for main current circuit

Front side

Device construction

Built-in device fixed built-in technique

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Overload release current setting

252 .. 630A

Number of poles

3

Power loss

30W

Number of auxiliary contacts as normally open contact

0

Integrated earth fault protection

Number of auxiliary contacts as normally closed contact

0

Motor drive integrated

Degree of protection (IP)

IP40

Complete device with protection unit

Number of auxiliary contacts as change-over contact

0

Motor drive optional

With switched-off indicator

Type of control element

Toggle

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.