Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • SCHNEIDER

Technical specifications

Adjustment range short-term delayed short-circuit release- - -A
Rated voltage690 - 690V
Power loss66W
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Overload release current setting400 - 1000A
Rated permanent current Iu1000A
Integrated earth fault protectionNo
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally open contact0
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1500 - 10000A
Complete device with protection unitYes
Type of control elementToggle
With integrated under voltage releaseNo
Type of electrical connection of main circuitScrew connection
DIN rail (top hat rail) mounting optionalNo
Number of poles3
Suitable for DIN rail (top hat rail) mountingNo
Motor drive integratedNo
Position of connection for main current circuitFront side
Motor drive optionalYes
Degree of protection (IP)IP40
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

33472

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • SCHNEIDER

Technical specifications

Adjustment range short-term delayed short-circuit release

- .. -A

Rated voltage

690 .. 690V

Power loss

66W

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Overload release current setting

400 .. 1000A

Rated permanent current Iu

1000A

Integrated earth fault protection

Number of auxiliary contacts as change-over contact

0

Number of auxiliary contacts as normally closed contact

0

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally open contact

0

With switched-off indicator

Adjustment range undelayed short-circuit release

1500 .. 10000A

Complete device with protection unit

Type of control element

Toggle

With integrated under voltage release

Type of electrical connection of main circuit

Screw connection

DIN rail (top hat rail) mounting optional

Number of poles

3

Suitable for DIN rail (top hat rail) mounting

Motor drive integrated

Position of connection for main current circuit

Front side

Motor drive optional

Degree of protection (IP)

IP40