Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • SCHNEIDER

Technical specifications

Release characteristicD
Built-in depth44.5mm
Rated insulation voltage Ui500V
Rated voltage400V
Rated current2A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V70kA
Frequency50 - 60Hz
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Degree of protection (IP)IP20
Width in number of modular spacings2
Connectable conductor cross section multi-wired1 - 16mm²
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Voltage typeAC/DC
Flush-mounted installationNo
Additional equipment possibleYes
Concurrently switching neutral conductorNo
Ambient temperature during operating-35 - 70°C
Pollution degree3
Current limiting class3
Number of poles (total)2
Over voltage category4
Number of protected poles2
Rated impulse withstand voltage Uimp6kV
Explosion-proofNo
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V70kA
Connectable conductor cross section solid-core1 - 25mm²
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

A9F85202

Main Product Image

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • SCHNEIDER

Technical specifications

Release characteristic

D

Built-in depth

44.5mm

Rated insulation voltage Ui

500V

Rated voltage

400V

Rated current

2A

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

70kA

Frequency

50 .. 60Hz

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Degree of protection (IP)

IP20

Width in number of modular spacings

2

Connectable conductor cross section multi-wired

1 .. 16mm²

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Voltage type

AC/DC

Flush-mounted installation

Additional equipment possible

Concurrently switching neutral conductor

Ambient temperature during operating

-35 .. 70°C

Pollution degree

3

Current limiting class

3

Number of poles (total)

2

Over voltage category

4

Number of protected poles

2

Rated impulse withstand voltage Uimp

6kV

Explosion-proof

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

70kA

Connectable conductor cross section solid-core

1 .. 25mm²

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.