A9F95116
Code: 1694360

A9F95116

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
-kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
-kA
Built-in depth
44.5mm
Number of protected poles
1
Rated current
16A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
25kA
Rated voltage
230V
Voltage type
AC/DC
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
15kA
Number of poles (total)
1
Rated impulse withstand voltage Uimp
6kV
Current limiting class
3
Frequency
50 .. 60Hz
Explosion-proof
Flush-mounted installation
Degree of protection (IP)
IP20
Concurrently switching neutral conductor
Width in number of modular spacings
1
Additional equipment possible
Connectable conductor cross section multi-wired
1 .. 16mm²
Connectable conductor cross section solid-core
1 .. 25mm²
Release characteristic
K
Over voltage category
4
Rated insulation voltage Ui
500V
Ambient temperature during operating
-35 .. 70°C
Pollution degree
3