Details

  • Earthing, lightning and surge protection
  • Surge protection device for power supply systems
  • 1 KOM
  • SCHNEIDER

Technical specifications

Voltage protection level N-PE1.5kV
System configuration DCNo
System configuration ITNo
Max. conductor cross section solid (solid, stranded)25mm²
Max. continuous voltage AC350V
Max. conductor cross section flexible (fine-strand)16mm²
Max. PV-voltage-V
Nominal voltage DC-V
Number of conductors (without earthing)2
Max. continuous voltage DC-V
Category type 2Yes
Voltage protection level L-N1.5kV
Signalling at the deviceOptic
Integrated backup fuseNo
With remote signalling contactYes
Construction size2 modular spacing
Mounting methodDIN rail (top hat rail) 35 mm
Voltage protection level1.5kV
System configuration TN-CYes
System configuration TTNo
System configuration TNNo
System configuration TN-SNo
Max. overcurrent protection device, parallel connection (fuse)80A
Short-circuit breaking capacity (Isccr)50kA
Max. overcurrent protection device, series connection (fuse)80A
Max. discharge surge current (8/20)65kA
System configuration TN-C-SNo
Leakage-current freeNo
Integrated short-circuit protectionNo
System configuration otherNo
Nominal discharge surge current (8/20)20kA
Nominal voltage AC350V
Degree of protection (IP)IP20
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user