Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • SCHNEIDER

Technical specifications

Built-in depth44mm
Rated voltage400V
Number of poles (total)4
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V15kA
Release characteristicC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V30kA
Rated insulation voltage Ui500V
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V15kA
Number of protected poles4
Rated current125A
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V15kA
Rated impulse withstand voltage Uimp6kV
Flush-mounted installationNo
Concurrently switching neutral conductorYes
Voltage typeAC
Pollution degree3
Frequency50 - 60Hz
Additional equipment possibleYes
Over voltage category4
Degree of protection (IP)IP20
Ambient temperature during operating-30 - 60°C
Connectable conductor cross section multi-wired1 - 35mm²
Width in number of modular spacings6
Current limiting class3
Connectable conductor cross section solid-core1.5 - 50mm²
Explosion-proofNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

A9N18481

Main Product Image

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • SCHNEIDER

Technical specifications

Built-in depth

44mm

Rated voltage

400V

Number of poles (total)

4

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

15kA

Release characteristic

C

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

30kA

Rated insulation voltage Ui

500V

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

15kA

Number of protected poles

4

Rated current

125A

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

15kA

Rated impulse withstand voltage Uimp

6kV

Flush-mounted installation

Concurrently switching neutral conductor

Voltage type

AC

Pollution degree

3

Frequency

50 .. 60Hz

Additional equipment possible

Over voltage category

4

Degree of protection (IP)

IP20

Ambient temperature during operating

-30 .. 60°C

Connectable conductor cross section multi-wired

1 .. 35mm²

Width in number of modular spacings

6

Current limiting class

3

Connectable conductor cross section solid-core

1.5 .. 50mm²

Explosion-proof

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.