Degree of protection (IP)IP20
With integrated auxiliary switchNo
Rated operating voltage690 - 690V
With integrated under voltage releaseNo
Adjustment range undelayed short-circuit release170 - 170A
Switch off techniqueThermomagnetic
Rated operation power at AC-3, 230 V3kW
Device constructionComplete device in housing
Phase failure sensitiveYes
Type of control elementPush button
With thermal protectionYes
Type of electrical connection of main circuitSpring clamp connection
Rated operation power at AC-3, 400 V5.5kW
Rated permanent current Iu14A
Overload release current setting9 - 14A
Rated short-circuit breaking capacity lcu at 400 V, AC15kA