Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation prot.
  • 1 KOM
  • SCHNEIDER

Technical specifications

Number of auxiliary contacts as normally open contact0
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as change-over contact0
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release1250 - 2500A
Adjustment range short-term delayed short-circuit release0 - 0A
With switched-off indicatorNo
Type of control elementRocker lever
Degree of protection (IP)IP30
Motor drive optionalYes
Overload release current setting175 - 250A
With under voltage releaseNo
Motor drive integratedNo
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitFront side
Type of electrical connection of main circuitScrew connection
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu250A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA