VCF6
Code: 1715621

VCF6

Number of switches
1
Version as emergency stop installation
Version as reversing switch
Max. rated operation voltage Ue AC
690V
Version as maintenance-/service switch
Rated operating voltage
690 .. 690V
Rated permanent current Iu
175A
Rated permanent current at AC-23, 400 V
21.8A
Rated permanent current at AC-21, 400 V
160A
Motor drive optional
Version as safety switch
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Rated operation power at AC-23, 400 V
45kW
Number of auxiliary contacts as normally open contact
0
Switching power at 400 V
90kW
Suitable for floor mounting
Motor drive integrated
Rated operation power at AC-3, 400 V
37kW
Number of auxiliary contacts as change-over contact
0
Voltage release optional
Rated short-time withstand current lcw
2.1kA
Conditioned rated short-circuit current Iq
10kA
Version as main switch
Colour control element
Red
Device construction
Built-in device fixed built-in technique
Interlockable
Suitable for front mounting 4-hole
Suitable for front mounting centre
Degree of protection (IP), front side
IP65
Type of electrical connection of main circuit
Screw connection
Type of control element
Turn button
Suitable for intermediate mounting
Suitable for distribution board installation