Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Motor drive integratedNo
With switched-off indicatorYes
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitBack side
Type of control elementPush button
Degree of protection (IP)IP31
Adjustment range undelayed short-circuit release1260 - 7560A
Adjustment range short-term delayed short-circuit release1260 - 6300A
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitRail connection
Overload release current setting315 - 630A
Number of auxiliary contacts as change-over contact2
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionNo
Complete device with protection unitYes
With under voltage releaseNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu630A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA