Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Overload release current setting500 - 1250A
Number of auxiliary contacts as change-over contact2
Power loss180W
Degree of protection (IP)IP31
Position of connection for main current circuitBack side
Motor drive integratedNo
Type of electrical connection of main circuitRail connection
Type of control elementPush button
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release750 - 12500A
Adjustment range undelayed short-circuit release2500 - 18750A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Rated permanent current Iu1250A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Related products
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user