Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
IZMX16N3-P10F-1

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
500 .. 1000A
Type of electrical connection of main circuit
Rail connection
Adjustment range undelayed short-circuit release
2000 .. 12000A
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
2000 .. 10000A
Number of auxiliary contacts as change-over contact
2
Rated voltage
690 .. 690V
Motor drive optional
Position of connection for main current circuit
Back side
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Degree of protection (IP)
IP31
Rated permanent current Iu
1000A
Motor drive integrated
Integrated earth fault protection
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
With under voltage release
DIN rail (top hat rail) mounting optional