Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Overload release current setting400 - 800A
Degree of protection (IP)IP31
Number of auxiliary contacts as change-over contact2
Type of control elementPush button
Position of connection for main current circuitBack side
Motor drive integratedNo
Type of electrical connection of main circuitRail connection
Device constructionBuilt-in device slide-in technique (withdrawable)
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Complete device with protection unitYes
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1600 - 9600A
Motor drive optionalYes
Adjustment range short-term delayed short-circuit release1600 - 8000A
Rated permanent current Iu800A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA