Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Degree of protection (IP)IP31
Position of connection for main current circuitBack side
Number of auxiliary contacts as change-over contact2
Motor drive integratedNo
Overload release current setting625 - 1250A
Adjustment range short-term delayed short-circuit release2500 - 12500A
Type of electrical connection of main circuitRail connection
Type of control elementPush button
With under voltage releaseNo
With switched-off indicatorYes
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release2500 - 15000A
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu1250A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA

Related products