Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally open contact0
Overload release current setting800 - 1600A
Number of auxiliary contacts as change-over contact2
Number of auxiliary contacts as normally closed contact0
Motor drive integratedNo
Position of connection for main current circuitBack side
Degree of protection (IP)IP31
With under voltage releaseNo
Type of control elementPush button
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release3200 - 16000A
Adjustment range undelayed short-circuit release3200 - 19200A
Integrated earth fault protectionNo
Type of electrical connection of main circuitRail connection
Complete device with protection unitYes
With switched-off indicatorYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Rated permanent current Iu1600A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA

Related products