  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally open contact0
Overload release current setting1600 - 3200A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact2
Degree of protection (IP)IP31
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release6400 - 38400A
Type of control elementPush button
With under voltage releaseNo
Motor drive integratedNo
Position of connection for main current circuitBack side
Type of electrical connection of main circuitRail connection
Adjustment range short-term delayed short-circuit release6400 - 32000A
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu3200A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA

Related products