IZMX40H4-P08F-1
Code: 1746298

IZMX40H4-P08F-1

Rated permanent current Iu
800A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
105kA
Overload release current setting
320 .. 800A
Adjustment range short-term delayed short-circuit release
480 .. 8000A
Device construction
Built-in device fixed built-in technique
Power loss
25W
Adjustment range undelayed short-circuit release
1600 .. 12000A
Number of auxiliary contacts as change-over contact
2
With switched-off indicator
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Integrated earth fault protection
With integrated under voltage release
Motor drive integrated
Type of electrical connection of main circuit
Rail connection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Complete device with protection unit
Degree of protection (IP)
IP31
Motor drive optional