Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu1000A
Suitable for DIN rail (top hat rail) mountingNo
Position of connection for main current circuitBack side
Number of auxiliary contacts as change-over contact2
Number of auxiliary contacts as normally closed contact0
Number of poles4
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of control elementPush button
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release2000 - 10000A
Number of auxiliary contacts as normally open contact0
Motor drive optionalYes
Type of electrical connection of main circuitRail connection
With switched-off indicatorYes
Degree of protection (IP)IP31
With under voltage releaseNo
Motor drive integratedNo
Overload release current setting500 - 1000A
Integrated earth fault protectionNo
Complete device with protection unitYes
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz105kA
Adjustment range undelayed short-circuit release2000 - 12000A

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

IZMX40H4-P10W-1

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

1000A

Suitable for DIN rail (top hat rail) mounting

Position of connection for main current circuit

Back side

Number of auxiliary contacts as change-over contact

2

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

Device construction

Built-in device slide-in technique (withdrawable)

Type of control element

Push button

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

2000 .. 10000A

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Type of electrical connection of main circuit

Rail connection

With switched-off indicator

Degree of protection (IP)

IP31

With under voltage release

Motor drive integrated

Overload release current setting

500 .. 1000A

Integrated earth fault protection

Complete device with protection unit

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

105kA

Adjustment range undelayed short-circuit release

2000 .. 12000A

Related products

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.