Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitBack side
Type of electrical connection of main circuitRail connection
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
With switched-off indicatorYes
Adjustment range undelayed short-circuit release2500 - 15000A
Number of auxiliary contacts as change-over contact2
Degree of protection (IP)IP31
Adjustment range short-term delayed short-circuit release2500 - 12500A
Overload release current setting625 - 1250A
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementPush button
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
With under voltage releaseNo
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu1250A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz105kA