Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Overload release current setting2000 - 4000A
Degree of protection (IP)IP31
Type of control elementPush button
Motor drive integratedNo
Position of connection for main current circuitBack side
Type of electrical connection of main circuitRail connection
Adjustment range short-term delayed short-circuit release8000 - 40000A
Number of auxiliary contacts as change-over contact2
Adjustment range undelayed short-circuit release8000 - 48000A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Integrated earth fault protectionNo
With under voltage releaseNo
With switched-off indicatorYes
Complete device with protection unitYes
Rated permanent current Iu4000A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz105kA
Related products