Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
IZMX40N3-P20W-1

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
2000A
Overload release current setting
1000 .. 2000A
Number of auxiliary contacts as change-over contact
2
Number of poles
3
Type of electrical connection of main circuit
Rail connection
With switched-off indicator
Rated voltage
690 .. 690V
Type of control element
Push button
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP31
Motor drive integrated
Adjustment range undelayed short-circuit release
4000 .. 24000A
Motor drive optional
Adjustment range short-term delayed short-circuit release
4000 .. 20000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Suitable for DIN rail (top hat rail) mounting
With under voltage release
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Complete device with protection unit