Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
IZMX40N4-P32F-1

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
3200A
With integrated under voltage release
Overload release current setting
1280 .. 3200A
Number of poles
4
Position of connection for main current circuit
Back side
Motor drive integrated
Rated voltage
690 .. 690V
Power loss
385W
Degree of protection (IP)
IP31
Number of auxiliary contacts as change-over contact
2
Type of electrical connection of main circuit
Rail connection
Type of control element
Push button
Adjustment range undelayed short-circuit release
6400 .. 48000A
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
1920 .. 32000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
With switched-off indicator
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Motor drive optional
Complete device with protection unit
Integrated earth fault protection