Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
IZMX40N4-V16F-1

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
2
Rated permanent current Iu
1600A
Degree of protection (IP)
IP31
Rated voltage
690 .. 690V
Number of poles
4
Overload release current setting
800 .. 1600A
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Motor drive optional
Adjustment range short-term delayed short-circuit release
3200 .. 16000A
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Back side
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
With switched-off indicator
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Adjustment range undelayed short-circuit release
3200 .. 19200A
Type of electrical connection of main circuit
Rail connection
Complete device with protection unit
Motor drive integrated
With under voltage release