Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Adjustment range undelayed short-circuit release380 - 630A
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release0 - 0A
Rated permanent current Iu63A
Number of auxiliary contacts as change-over contact0
Type of control elementRocker lever
With integrated under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitFrame clamp
DIN rail (top hat rail) mounting optionalYes
Rated voltage440 - 440V
Position of connection for main current circuitFront side
Motor drive integratedNo
Motor drive optionalNo
With switched-off indicatorNo
Complete device with protection unitYes
Overload release current setting50 - 63A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz25kA
Number of poles3
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP20
Integrated earth fault protectionNo
Number of auxiliary contacts as normally closed contact0

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMB1-A63-NA

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Adjustment range undelayed short-circuit release

380 .. 630A

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

0 .. 0A

Rated permanent current Iu

63A

Number of auxiliary contacts as change-over contact

0

Type of control element

Rocker lever

With integrated under voltage release

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Frame clamp

DIN rail (top hat rail) mounting optional

Rated voltage

440 .. 440V

Position of connection for main current circuit

Front side

Motor drive integrated

Motor drive optional

With switched-off indicator

Complete device with protection unit

Overload release current setting

50 .. 63A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

25kA

Number of poles

3

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP20

Integrated earth fault protection

Number of auxiliary contacts as normally closed contact

0

Related products