Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

With integrated under voltage releaseNo
Overload release current setting125 - 160A
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitScrew connection
Motor drive optionalYes
Degree of protection (IP)IP20
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorNo
Device constructionBuilt-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release0 - 0A
Complete device with protection unitYes
Position of connection for main current circuitFront side
DIN rail (top hat rail) mounting optionalYes
Adjustment range undelayed short-circuit release960 - 1600A
Integrated earth fault protectionNo
Type of control elementRocker lever
Motor drive integratedNo
Rated permanent current Iu160A
Number of poles3
Rated voltage440 - 440V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz25kA

Related products