Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Type of control elementRocker lever
Type of electrical connection of main circuitFrame clamp
Overload release current setting225 - 225A
With integrated under voltage releaseNo
Position of connection for main current circuitFront side
Motor drive integratedNo
Number of auxiliary contacts as change-over contact0
Degree of protection (IP)IP20
With switched-off indicatorNo
Adjustment range undelayed short-circuit release1500 - 2500A
Adjustment range short-term delayed short-circuit release0 - 0A
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalYes
Complete device with protection unitYes
Motor drive optionalYes
Rated permanent current Iu225A
Number of poles3
Rated voltage440 - 440V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz25kA

Related products