Technical specifications

Rated permanent current Iu50A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitScrew connection
Rated voltage690 - 690V
Suitable for DIN rail (top hat rail) mountingNo
Overload release current setting40 - 50A
DIN rail (top hat rail) mounting optionalYes
Integrated earth fault protectionNo
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release0 - 0A
Number of auxiliary contacts as change-over contact0
Adjustment range undelayed short-circuit release300 - 500A
With integrated under voltage releaseNo
With switched-off indicatorNo
Number of poles3
Complete device with protection unitYes
Motor drive optionalYes
Number of auxiliary contacts as normally closed contact0
Motor drive integratedNo
Degree of protection (IP)IP20
Position of connection for main current circuitFront side
Type of control elementRocker lever

Related products

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMH2-A50-NA

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

50A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Screw connection

Rated voltage

690 .. 690V

Suitable for DIN rail (top hat rail) mounting

Overload release current setting

40 .. 50A

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

0 .. 0A

Number of auxiliary contacts as change-over contact

0

Adjustment range undelayed short-circuit release

300 .. 500A

With integrated under voltage release

With switched-off indicator

Number of poles

3

Complete device with protection unit

Motor drive optional

Number of auxiliary contacts as normally closed contact

0

Motor drive integrated

Degree of protection (IP)

IP20

Position of connection for main current circuit

Front side

Type of control element

Rocker lever

Related products