

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated voltage
690 - 690V
Rated permanent current Iu
150A
Adjustment range short-term delayed short-circuit release
300 - 1500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1800 - 1800A
DIN rail (top hat rail) mounting optional
Yes
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
No
With switched-off indicator
No
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Position of connection for main current circuit
Front side
Motor drive optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
Degree of protection (IP)
IP20
Overload release current setting
150 - 150A
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
No
Type of control element
Rocker lever
Suitable for DIN rail (top hat rail) mounting
No
Related products
From same serie
NZMH2-VEF150-NA

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated voltage
690 .. 690V
Rated permanent current Iu
150A
Adjustment range short-term delayed short-circuit release
300 .. 1500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1800 .. 1800A
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as normally closed contact
0
Integrated earth fault protection
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Position of connection for main current circuit
Front side
Motor drive optional
Complete device with protection unit
Motor drive integrated
Degree of protection (IP)
IP20
Overload release current setting
150 .. 150A
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
Type of control element
Rocker lever
Suitable for DIN rail (top hat rail) mounting
From same serie
Related products
We use cookies to enhance your experience.