Technical specifications
Rated permanent current Iu
200A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
200 - 200A
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Front side
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Yes
Type of control element
Rocker lever
Number of poles
3
Motor drive integrated
No
Complete device with protection unit
Yes
With switched-off indicator
No
Degree of protection (IP)
IP20
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
400 - 2000A
Adjustment range undelayed short-circuit release
2400 - 2400A
Related products
NZMH2-VEF200-NA

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
200A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
200 .. 200A
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Front side
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Motor drive optional
Type of control element
Rocker lever
Number of poles
3
Motor drive integrated
Complete device with protection unit
With switched-off indicator
Degree of protection (IP)
IP20
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
400 .. 2000A
Adjustment range undelayed short-circuit release
2400 .. 2400A