Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
NZMH4-AEF1200-NA

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Adjustment range undelayed short-circuit release
2400 .. 14400A
Adjustment range short-term delayed short-circuit release
0 .. 0A
With integrated under voltage release
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
1200 .. 1200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of poles
3
Position of connection for main current circuit
Front side
With switched-off indicator
Integrated earth fault protection
Type of electrical connection of main circuit
Screw connection
Rated voltage
690 .. 690V
Type of control element
Rocker lever
Rated permanent current Iu
1200A
Number of auxiliary contacts as change-over contact
0
Degree of protection (IP)
IP20
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Motor drive optional
DIN rail (top hat rail) mounting optional