Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
NZMN2-VEF175-BT-NA

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
175A
Number of auxiliary contacts as change-over contact
0
Rated voltage
690 .. 690V
Motor drive integrated
Type of electrical connection of main circuit
Frame clamp
Motor drive optional
DIN rail (top hat rail) mounting optional
Complete device with protection unit
With under voltage release
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Integrated earth fault protection
Degree of protection (IP)
IP20
Type of control element
Rocker lever
Number of poles
3
Overload release current setting
175 .. 175A
Adjustment range undelayed short-circuit release
2100 .. 2100A
Adjustment range short-term delayed short-circuit release
350 .. 1750A
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA