Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •EATON
Technical specifications
Related products
NZMN4-VEF1000-NA

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
1000A
With integrated under voltage release
Number of poles
3
Overload release current setting
1000 .. 1000A
Number of auxiliary contacts as change-over contact
0
Rated voltage
690 .. 690V
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Motor drive integrated
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
37kA
Adjustment range short-term delayed short-circuit release
2000 .. 10000A
Adjustment range undelayed short-circuit release
2000 .. 12000A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Motor drive optional
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Complete device with protection unit